| HP | 115 V | 200 V | 208 V | 230 V |
|---|---|---|---|---|
| 1/6 | 4.4 | 2.5 | 2.4 | 2.2 |
| 1/4 | 5.8 | 3.3 | 3.2 | 2.9 |
| 1/3 | 7.2 | 4.1 | 4.0 | 3.6 |
| 1/2 | 9.8 | 5.6 | 5.4 | 4.9 |
| 3/4 | 13.8 | 7.9 | 7.6 | 6.9 |
| 1 | 16 | 9.2 | 8.8 | 8.0 |
| 1.5 | 20 | 11.5 | 11.0 | 10.0 |
| 2 | 24 | 13.8 | 13.2 | 12.0 |
| 3 | 34 | 19.6 | 18.7 | 17.0 |
| 5 | 56 | 32.2 | 30.8 | 28.0 |
| 7.5 | 80 | 46.0 | 44.0 | 40.0 |
| 10 | 100 | 57.5 | 55.0 | 50.0 |
| Portion of Lighting Load (VA) | Demand Factor |
|---|---|
| First 3,000 VA | 100% |
| Next 117,000 VA (3,001 – 120,000) | 35% |
| Over 120,000 VA | 25% |
Source: PEC 2017 Table 2.20.3.3 — applies to general illumination in dwelling units. Small appliance and laundry branch-circuit loads may be included.
| Number of Dryers | Demand Factor |
|---|---|
| 1 – 4 | 100% |
| 5 | 80% |
| 6 | 70% |
| 7 | 65% |
| 8 | 60% |
| 9 | 55% |
| 10 + | 50% |
Minimum load per dryer = 5,000 VA (PEC Rule). This calculator uses 100% demand factor regardless of quantity — conservative approach for residential estimation.
| Qty | Col A — Max Demand (kW) (> 8.75 kW units) |
Col B — Demand Factor (< 3.5 kW units) |
Col C — Demand Factor (3.5 – 8.75 kW units) |
|---|---|---|---|
| 1 | 8 kW | 80% | 80% |
| 2 | 11 kW | 75% | 65% |
| 3 | 14 kW | 70% | 55% |
| 4 | 17 kW | 66% | 50% |
| 5 | 20 kW | 62% | 45% |
| 6 | 21 kW | 59% | 43% |
| 7 | 22 kW | 56% | 40% |
| 8 | 23 kW | 53% | 36% |
| 9 | 24 kW | 51% | 35% |
| 10 | 25 kW | 49% | 34% |
| 11 | 26 kW | 47% | 32% |
| 12 | 27 kW | 45% | 32% |
| 13 | 28 kW | 43% | 32% |
| 14 | 29 kW | 41% | 32% |
| 15 | 30 kW | 40% | 32% |
| 16 | 31 kW | 39% | 28% |
| 17 | 32 kW | 38% | 28% |
| 18 | 33 kW | 37% | 28% |
| 19 | 34 kW | 36% | 28% |
| 20 | 35 kW | 35% | 28% |
| 21 | 36 kW | 34% | 26% |
| 22 | 37 kW | 33% | 26% |
| 23 | 38 kW | 32% | 26% |
| 24 | 39 kW | 31% | 26% |
| 25 | 40 kW | 30% | 26% |